TrendMassTer® Model TM6GNX
Thermal Mass Flow Meter

  • Thermal mass flow meter specifically designed to operate in gasses.
  • Wide operating temperature range -58°F to +650°F (-50°C to +350°C).
  • Direct mass flow, no secondary measurements.
  • Low pressure drop without restriction
  • Two year workmanship warranty.
  • Free of all moving parts that can stick, coat or fail.
  • Response time as low as .5 seconds media dependent.
  • LED Backlit LCD Display.
  • Constant Data Update.

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

TrendMassTer® TM6000

SPECIFICATIONS

SENSORS

Type:
All Metal – Twin tip all metal body
316L stainless steel with Hastelloy C twin tips.

Process Connection:
Compression Fitting for use in line sizes
2 to 48 inches and larger.
Spool piece for use in line sizes .75 to 6 inches
with 150 or 300 lb flanges.
Special process connections available; contact factory

Operating Temperature Range:
Standard: -58 to 300 °F ( -50 to 150 °C)
Medium Temperature: to 480 °F ( 250 °C)
High Temperature: to 650 °F ( 350 °C)

Operating Pressure Range:
To 3000 PSIG.

ELECTRONICS

Power:
AC 100 to 240 VAC; 47 to 63 hz @ 15 watts.
DC 18 to 30 VDC @ 24 watts.

Operating Temperature Range:
Standard 32° to 122° F (0° to 50° C )
Blind Display -20° to 185° F (-29° to 85° C )

Outputs:
Analog: dual 4 to 20 mA, isolated with external loop power.
Digital: RS485 Standard with Ethernet as an option.
Switched: Dual open drain.
Display: 32 character LCD display (16×2 LED backlit).

Diagnostics:
Sensor and electronics monitored once per second.
Fault signal transmitted if any abnormality occurs.
User selected upscale or downscale on 4 to 20 mA.

Communications:
Simple 4 button key pad for field configuration when ordered with local display.
RS485 standard configuration via control system or laptop.

Enclosure:
Double sided non explosion proof or explosion proof.
CLASS I, DIV 1, GROUPS B, C, D.
CLASS II, DIV 1 GROUPS E, F, G.
CLASS III
UL1203; CSA C22.2 No. 30 & CSA C22.2 No. 25
NEMA: Type4X.
ATEX (FLAMEPROOF – DEMKO)
II 2G Ex d IIB+H2
II 2 D Ex tD A20
IP66
IECEx (FLAMEPROOF – UL)
Ex d IIB + H2
IP66
EN60079-0: 2006, EN60079-1
EN61241-0: 2006, EN61241-1
EN60529

IEC60079-0:2004 & IEC60079-1
IEC60529

INSTRUMENT

Temperature Effect:
0.1% per degree C within ± 20°C.

Response Time:
0.5 to 30 seconds

Accuracy:
1% of rate to +0.5% of Full Scale

Repeatability
±1% of reading

Available Approvals:
No approvals – general purpose areas only

OPTIONS