MODEL VS5100
Full Featured VERSA-SWITCH®
MASS FLOW - LEVEL - TEMPERATURE

  • Simple Field configurable unit for mass flow, level, and/or temperature of liquids or gases.
  • Wide operating temperature range -100°F to +850°F
    (-70°C to +458°C).
  • Field selectable operating power 11OVAC, 220VAC, or 24VDC.
  • Removable plug in electronics.
  • Can be configured with 2 independent outputs, such as level or mass flow with temperature or two mass flow rates.
  • Can be used for either gas or liquid applications including interface detection.
  • Self heating sensor design. No separate heater to establish thermal differential.
  • Two Year Workmanship Warranty.
SPECIFICATIONS

Sensor

Type:
Thermal Differential, Dual RTD Sensors.

Process Connection:
Standard 0.75 inch MNPT.
Optionally 0.25 inch and larger MNPT and various other process connections such as sanitary and flanges.

Insertion Length:
Standard 2.0 inch.
Optionally 0.5 inch or greater.

Operating Temperature Range:
Standard -1OO°F to 390°F
(-70°C to +200°C).
Medium Temperature to +572°F (+300°C).
High Temperature to +850°F (+458°C).

Materials of Construction:
Standard 316 Series Stainless Steel.
Optionally Hastelloy, Monel, Inconel and other exotic materials.

Operating Pressure Range:
Standard to 3000 psia
(207 bar)

Electronics

Power:
Standard Field selectable 110VAC, 220 VAC, or 24 VDC at 3 watts (No heater power required). Optionally 24 VAC

Operating Temperature Range:
Standard -40°F to+140°F
(-40°C to+60°C).
Optionally Remote electronics for use in higher temperature environments.

Outputs:
Independent primary relay DPDT and secondary relay SPDT, contacts rated at 5 amp, 250 VAC with fail safe capability; built in time delay 0 to 300 seconds for each channel.

Self-Test:
Integral and automatic during power up.

Failure Alarm Option:
Continuous monitoring circuit to alarm should a failure condition of any sensor, component, wiring, or power occur. (Uses one or two channels of the VS5100)

Enclosure:
Explosion proof; NEMA 3, 4, 7, and 9:CSA, FM, UL, CENELEC, and EECS approved.

Instrument

Operating Range:
Flow 0.01 to 5.0 fps in liquids and 0.1 to 500 fps in gases. Level change as small as .-3 inch. Temperature -70°C to +458°C +/- 1°C.

Response Time:
Media dependent 0.5 to 10 seconds.

Approvals:
FM and CSA

Additional information may be obtained by contacting:

www.deltamcorp.com

DELTA M Corporation
1003 Larsen Drive
Oak Ridge, TN 37830

Phone: 1-800-922-0083
E-mail: technicalsales@deltamcorp.com